Cleaning of the FAD100FILTER filter meshes
The complete cleaning of the filter meshes requires their removal from the housing.
The removal of the FAD100FILTER filter meshes ([A]) must be carried out by pressing on their tabs ([B]) and by unthreading through the appropriate opening ([C]). For the cleaning process, the use of cans of “compressed air” normally used for cleaning electronic devices is recommended. It is recommended to hold the can nozzle approximately 5cm from the mesh. If necessary, use a clean brush with soft bristles. If it is not possible to clean the filters completely or if they are damaged, replace them. |
A high quantity of dust or dirt on the meshes, or the presence of a contamination fault, suggests the need to clean the interior of the detector module (sampling chamber).
For this kind of intervention also, the use of cans of “compressed air” is recommended. Holding the can nozzle approximately 5cm from the inlet/outlet vents, spray air into the detector module.